DC Balanced Reactor
    Variable Frequency Drive
    DC Flat Wave Reactor
    Input Reactor
    Output Reactor
    Energy Feedback Reactor
    Reactor of PMSM
    Rotor Inverter BOOST Reactor
    Dv/dt Filter
    Sine Wave Filter
    Passive Harmonic Filter
    LCL Filter
    EMC Filter
    Power Quality
    SVG Reactor
    APF Reactor
    Three Phase Series Detuning Reactor
    Three Phase Series Tuned Reactor
    Single-phase series detuning reactor
    New Energy
    Wind Power Filter Reactor
    Photovoltaic Filter Reactor
    Photovoltaic Isolation Transformer
    Transformer
    Rectifier Transformer
    Power Frequency Transformer
    Energy Consumption Braking
    Braking Unit
    Wirewound Resistor
    Aluminum-enclosure Resistor
    Braking Resistance Box
    Braking Resistance Cabinet
    Electric Vehicle
    BOOST Reactor For EV
    PFC Reactor for Charger
    High Frequency Reactor
    High Frequency Transformer

    Recommend

    Explosion-proof Feedback Reactor

    Time:2024-01-19     Visits:5

    Circuitry application: 

            Installed at the input side of the explosion-proof inverter PWM rectifier in mining industry, reduce the higher harmonic current caused by the switching frequency ripple current.

    201807251822027150.png

    Performance features:


      Rated voltage

      AC690V/AC1140V,50HZ  

      Insulation grade

      H

      Noise

      ≤70 d B

      Electricstrength

      AC4200V  50Hz  5s  leakage current≤5m A

      Ambient temperature

      -25℃~75℃,explosion-proof  

      Operative norm

      GB10229-88 reactor、IEC289:1987 reactor、JB9644-1999 reactor for transmission semiconductor      



    Dimensions and technical parameter:

    201807251822123557.png


    Technical parameter of explosion-proof feedback reactor


    Explosion-proof reactor, System voltage: 3-AC690V,50Hz,explosion-proof series frequency converter,                                    Insulation level: H; Ceiling of reactor temperature rise≤70K-80K

    Specifications and   models

    Figure  No.

    Carrier frequency(KHz)

    Power of frequency converter (kW)

    Rated current(A)

    Inductance   (mH)

    Weight   (KG)

    Dimensions(mm)

    W

    D

    H

    WO

    DO

    A*B

    FHCL-0090-EISC-150B

    A

    2

    75

    90

    1.5

    137.7 

    430

    260

    410

    240

    210

    14*28

    FHCL-0110-EISC-120B

    2

    90

    110

    1.2

    151.9

    430

    270

    410

    240

    220

    14*28

    FHCL-0150-EISC-900C

    2

    110

    150

    0.9

    189.7

    430

    270

    510

    240

    220

    14*28

    FHCL-0200-EISC-700C

    B

    2

    160

    200

    0.7

    221.9

    480

    270

    540

    200

    220

    14*28

    FHCL-0250-EISC-550C

    2

    200

    250

    0.55

    260.8

    480

    280

    660

    200

    220

    14*28

    FHCL-0300-EISC-450C

    2

    250

    300

    0.45

    270.9

    480

    305

    660

    200

    220

    14*28

    FHCL-0400-EISC-450C

    1.5

    355

    400

    0.45

    360.7

    540

    350

    690

    220

    240

    14*28

    FHCL-0480-EISC-380C

    1.5

    450

    480

    0.38

    419.3

    600

    360

    710

    240

    240

    14*28

    FHCL-0600-EISC-300C

    1.5

    560

    600

    0.3

    521.8

    660

    390

    730

    260

    250

    14*28

    FHCL-0800-EISC-230C

    1.5

    710

    800

    0.23

    761.2

    720

    470

    780

    280

    310

    14*28

    Explosion-proof reactor, System voltage:3-AC1140V,50Hzexplosion-proof series frequency converter,                                              Insulation level: H; Ceiling of reactor temperature rise≤70K-80K

    Specifications and   models

    Figure  No.

    Carrier frequency(KHz)

    Power of frequency converter (kW)

    Rated current(A)

    Inductance   (mH)

    Weight (KG)

    Dimensions(mm)

    W

    D

    H

    WO

    DO

    A*B

    FHCL-0150-EISC-160B

    B

    2

    200

    150

    1.6

    273.6

    480

    290

    660

    200

    230

    14*28

    FHCL-0200-EISC-120B

    2

    280

    200

    1.2

    331.3

    540

    340

    690

    220

    230

    14*28

    FHCL-0250-EISC-120B

    1.5

    355

    250

    1.2

    389.2

    600

    345

    710

    240

    230

    14*28

    FHCL-0300-EISC-980C

    1.5

    450

    300

    0.98

    441.0

    600

    360

    710

    240

    240

    14*28

    FHCL-0350-EISC-840C

    1.5

    500

    350

    0.84

    491.8

    660

    390

    730

    260

    240

    14*28

    FHCL-0400-EISC-735C

    1.5

    630

    400

    0.735

    567.5

    720

    470

    780

    280

    240

    14*28

    FHCL-0480-EISC-613C

    1.5

    710

    480

    0.613

    752.0

    720

    470

    780

    280

    310

    14*28


    Remarks: A/B/C stand for three-phase input side;X/Y/Z stand for output side.



    • Previous:没有了!
    • Next:没有了!

    Related Products